What makes a successful Operator Screen (HMI)?
Get it wrong, your operator misses an indication, you lose money, or worse, someone is injured.
Good HMI Design?

Bad HMI Design?

This article provides engineers with an introduction to designing screen graphics. Here's a quick summary:
Display pages need to be clear, easy to use and legible across a control desk:
-
Backgrounds - use muted tones – light grey is good.
-
Shadowing
is a recommended method for subdividing a display.
-
Background graphics should use muted tones, alarm colours should be avoided.
-
Use black
outlines to highlight objects.
-
Text –
use a standard font, which will be available on all PC’s.
-
Use
San serif fonts for on-screen clarity – e.g. Arial.
-
Text size
needs to be large enough to read at a distance e.g. Arial 16.
-
More
detailed text should be added as pop-up windows or ‘tool-tips’.
-
System
Alarm status should be visible on all displays.
-
Alarm
status should be displayed across the top of the display.
-
Alarm
colours will follow the convention: Red = alarm, Yellow = warning, green =
status OK.
-
For
Alarms - use additional non-colour dependent indications; position, text,
etc.
-
Flashing
of unaccepted alarms and automatic screen switching on alarm should be
avoided.
-
Sounds
are a good method for highlighting and prioritising alarms.
-
Dynamic
data should be positioned on scanned areas of the screen; i.e. across the
top, centrally and lower right.
-
Data
should be grouped logically.
-
Data
values should be clear & units should be obvious (but not repeated with
every value).
-
Data
Resolution should be appropriate to use, avoid too many decimal values;
546.45 C is pointless and unclear.
-
If red &
green are used for ‘Running’ & ‘Stopped’ indications, add text to make
it clear.
-
Plant
status indication must not rely solely upon colour changes.
-
Colour
combinations should be chosen with care and use appropriate colours and
contrasts.
-
Navigation buttons should be obvious and large enough to select quickly.
-
‘Next
Screen’ button should be ideally placed at the lower right side of the
screen.
-
A ‘Home /
Overview’ button should appear on each screen (ideally lower left corner).
-
Other
navigation buttons are best placed at the bottom of screen.
-
Control
buttons must invoke a ‘confirm action’ dialog box.
-
All pages
must have a consistent look & feel. Navigation buttons should be in the
same place.
-
Everything should line up.
To learn more,
read the rest of this article...
All modern control room systems use
visual displays to convey information to plant operators; often it is the
primary source of operational data. The clarity of these displays can determine
how well the plant is run; lack of information can result in poor operational
efficiency, excessive wear and tear and, in extreme cases, failure to see a
problem may be dangerous.
Display clarity becomes doubly important
when multiple VDU’s compete for an operator’s attention especially when
different displays have different purposes and are designed by different vendors
to differing standards. Often by engineers who have no training in design and
little experience of working in control rooms.
Remember also that whilst the designer
will sit close up in front of the screen, in use control-room VDUs will be
viewed at distance along a desk or even across the room. Whilst detail will be
lost, the presence of a plant problem should be evident at a distance – even if
the operator has left his spectacles at home!
Our objective here is to provide some
guidelines for screen design so that common pitfalls can be avoided and the
customer gets user-friendly displays, which are legible, useful and fit for
purpose.
Before designing any screen it is useful to understand how a user will use it.
Generally, users will scan a screen in the same way as they would scan a page in
a magazine, which in the west means from the top left corner to the right and
reading down the screen. Unlike a book, we have no lines to guide us, so we
usually only do 2 or 3 incomplete scans of the screen as suggested in example
below.

In taking
this into account, the display designer should ensure that important items
should be on the ‘scan’ line. Alarms should therefore be across the top of the
page, key data in centre right and maybe buttons and controls on the lower
right. Whilst supporting graphics and the company logo are better placed on the
lower left of the screen.
Before deciding what to put on a display
it is necessary to have some understanding of how colour can be used. Colour is
a powerful tool for enhancing visibility of key data. However excessive use of
colour can make a page confusing or overwhelming.
On-screen colours are created from 3
primary colours; Red, Green & Blue and the secondary colours; Cyan, Magenta and
Yellow are created from pairs of primary colours.
A colour wheel is often used to
demonstrate the relationship between colours. Example:

Complementary contrast is created by
positioning a secondary colour with the primary colour from the opposite side of
the wheel. Example:

Whilst useful to create impact, using
the colours together can make it difficult for the eye to focus.
Contrast of hue created from pairs of
adjacent colours can be more subtle, with pairs of secondary colours (cyan,
yellow, magenta) producing higher contrasts than pairs of primary colours (red,
green, blue).
Example:

The eye senses primary colours via the
cones, which are sensitive to red, green or blue light, as there are fewer blue
cones then our perception of blue is less. This is why thin blue lines are more
difficult to see. Blue should be avoided for small display objects however blue
does make a good background colour.
In selecting colours for a screen it is
essential to agree colours for plant status and alarms.
The preferred colour convention,
following the standard for safety signs (BS 5378) defines:
-
Red = stop, prohibition, danger
-
Yellow = caution, risk of danger
-
Green = safe condition
-
Blue = mandatory action.
Any screen design should ensure that
these key safety colours are clearly visible on the VDU and that these colours
are not overused for other purposes. Large blocks of primary colours, e.g. red,
should be avoided because they will cause complimentary colour image retention
on the retina. Try it for yourself; if you look at an area of bright red then
look at a white wall you will see the same image in green.
Designers also need to be aware that 1
in 12 men have some degree of colour blindness. This normally means that there
is some confusion in the perception of reds and greens (also yellows, oranges, &
browns) which mean that screen designs should not solely rely on colour to
indicate plant condition.
Whilst black and white provide good
colour contrast for text they produce too much glare and do not provide a good
background for a range of colours. Muted tones are best for backgrounds, greys,
browns and blues; these provide a good contrast for the brighter colours used
for important dynamic data, such as red, yellow, green, magenta or white.
Different background colours can
sometimes be used to good effect to immediately identify groups of screens. For
example, light grey may be used for the main plant, very light brown for the oil
tank farm, light blue for the water plant.
The use of subtle shading to create the
illusion on raising or lowering a section of the display can be used with great
effect to differentiate areas of the display.
Screen displays often include a
representation of the process plant. When well done, these can often help the
operator to immediately visualise the plant and the location of the
measurements. However too much detail can clutter the display and make it
difficult to see the important dynamic data, so keep it simple.
Muted tones are best used for plant
representations. Large areas of strong colours will detract from important
dynamic data. A good method to make items stand out is to outline the object in
black because the eye can easily see a black shape.
Photographs of the plant are sometimes
used as backgrounds; often these photographs are poorly lit and invariably
contain too much detail and produce very cluttered backgrounds with little
opportunity to optimise colour contrasts. Photographs should only be used in
exceptional circumstances and should be of good quality.
Sometimes background pictures can be
enhanced by the use of graphics from a wide range of graphical object
libraries. To add a series of 3D cylindrical tanks in shades of grey, can make
a display instantly identifiable, but adding 3D images of pipes, pumps, valves,
etc. adds little and will make the display too cluttered.
The temptation to create realism in a
background should be avoided, unless you are especially gifted. It is virtually
impossible to create good perspective, scale and shading. It will take a long
time to produce and the results will be disappointing. Realism is best avoided.
Perhaps the most common complaint about
displays is that the text is difficult to read, which is shame because text is
the most versatile way of conveying information to an operator.
There are hundreds of fonts available
but a few simple ground rules will avoid problems. Select a common font, one
that will exist on all computers, such as Arial, Helvetica, System, etc. If you
are designing for a Windows operating system and you use an unusual font you may
find that when all your careful work is moved onto a different PC that all fonts
will be re-mapped. Unexpected gothic script in operator displays is not often
welcomed!
Fonts are normally classified as ‘Serif’
and ‘San-Serif’. A serif refers to the curly bits at the end of each letter,
which lead the eye onto the next letter. Books and newspapers will almost
certainly be set in a Serif font in the body text. However, due to the
resolution of most VDU screens, it is better to use a San-Serif font such as
Arial;
because the resolution is not good enough to clearly render the detail of a
Serif font.
Having selected a font the next task is
to decide on a size. Basically, it should be possible to read key information
from several feet away without the need for reading glasses (an affliction
suffered by many of us over the age of 45!). Arial at 16 point should be a
good starting point. Up to 2 larger sizes should be selected for labels and
headings. Once you have selected a basic style – stay with it and avoid the
temptation to use different fonts or more than 3 sizes. If you find you need to
provide more detail in your text, use a pop-up window or ‘tool-tip’ so that the
user can select to see the additional text.
TOO MUCH UPPER-CASE TEXT CAN BE
DIFFICULT TO READ AND CAN CAUSE EYE STRAIN, ESPECIALLY IF AN UNDERLINE IS
USED. Upper
case should be reserved for headings. Text should be in lower case with the
first letter of the leading word a capital. It can sometimes be a problem to
know where to put capitals – I favour ‘Exhaust Valve Temperatures’ rather
than ‘Exhaust valve temperatures’ but which ever you choose, you should
be consistent.
Text, and especially data values, should
be grouped in areas of the screen. Randomly distributing data values around a
picture makes it difficult to scan for data values. If you want the user to
compare data values, then put them next to each other in a table. If you have
several tables with the same data types, e.g. temperature, pressure, speed;
ensure that the data is presented in the same order in each table.
Care should be taken with units. It is
important to know that pressure is displayed in millibars but writing ‘mBar’
next to every measurement is unnecessary and clutters the display.
Avoid unnecessary decimal places. The
displayed Data Resolution should be appropriate to use; 546.45 C is pointless
and difficult to read, (the accuracy of measurement is probably limited to +/-
2C).
Subtle changes in background relief can
often be used to enhance the presentation of text and data. If you choose to
include this in your design, it is important to ensure that you are consistent.
The key aspect of an HMI display is the
dynamic plant data. There are 2 basic types of dynamic data: Alarms and normal
Plant Status data.
Alarm status for the overall plant,
preferably organised into groups, should be visible on every screen and there
should be a simple navigation route to access the screen containing additional
details about the alarm. The alarm colours should follow the safety convention:
-
Red = stop, prohibition, danger
-
Yellow = caution, risk of danger
-
Green = safe condition
-
Blue = mandatory action.
As 1 in 12 men have some form of
colour-blindness, which can affect the perception of red and green, colour
cannot be used as the sole indicator of alarms. Any colour change must be
supplemented with a pictorial change and if the alarm is critical, an audible
alert.
Pictorial changes could include shape
changing, a change in the position of an indicator, having additional text or
objects appear on an alarm. Flashing of unaccepted alarms is very irritating
and stressful and should be avoided. Similarly, automatic changing of displays
should be avoided – to have a page disappear when you are working on it is
irritating and in extreme cases a cascade of alarms can produce so many screen
refreshes, an operator can be locked out of the system.
Audible alerts can be very useful,
especially if the system is able to create multiple tones and pitches. These
tones can be used to transmit the importance of an alarm, research has shown
that a high pitched, fast pulsing sound automatically conveys urgency, whereas a
lower pitch, slow pulsing sound is less urgent.
Whatever convention is used, alarms
should be placed where they can be easily seen, our preference is along the top
of the screen.
Whilst conventions are generally well
defined for alarms, some designers have problems when using colours for plant
status. Some are tempted to use green for go to indicate running plant and red
for stopped, whereas the alarm logic would suggest using red for dangerous,
running plant and green for safe, stopped plant. The convention in the power
industry is RED for RUNNING, but to be sure (and to account for colour
blindness) plant status should always be indicated by another means preferably
text – ‘Running’.
If there is risk of confusing a red status indicator for an alarm then other
colour combinations should be used.
To use a VDU system, the operator must
be able to change between pages quickly and easily. With the wide acceptance
of Microsoft Windows, the operator control device of choice are ‘mice’ or
similar pointing devices, which have largely superseded keyboards as a primary
navigation tool. Perhaps the most intuitive pointing device is the touch
screen.
Whatever the choice of pointing device,
the screen ‘hot spot’ must be obvious and large enough to be hit easily. There
are 2 main preferred methods of denoting a ‘hot spot’; the most obvious is to
add a button to the display. These should be clearly labelled to indicate the
effect of the button. The other approach is to embed the hot-spot in the
picture. This can be used to great effect in an overview display showing a
schematic layout of the site; ‘clicking’ over any area will switch the screen to
a more detailed display.
Navigation between displays should be
simple, obvious and quick, and will normally be organised in a logical tree
structure. The next step in a navigation sequence should always be the most
obvious; the lower right hand part of the page is a good place to put a ‘next
step’ button. It should also be possible to back-track and return to the
previous display. All screens should also have a button or hot-spot to reset
the screen to the top-level display, often called the ‘Overview’. This is the
equivalent of a ‘Home’ page on a well-designed web-site. This ‘Overview’ button
need not be too obvious and should be located in the same position on every
page; the bottom left is often preferred.
If possible, navigation buttons should
be grouped together to make it easy for the operator to use them without having
to move a mouse or trackball too far. If the user is expected to routinely
switch between two or more screens, it is a nice idea to locate the button for
the next screen in the sequence at same point on each screen, so that the user
can click quickly between displays without moving the pointer.
Where buttons and hot-spots are used for
control, then a pop-up window should be used to confirm the action selected:
e.g. ‘Start Feed Pump – OK or Cancel’. This avoids accidentally activating
plant and allows the new user to explore the system without fear of causing
damage or injury.
There are no absolutes when designing
HMI displays, and everyone will have their own preferences.
The following screens show two
representations of the same plant.
The 'Good'
screen follows the guidelines as described with a good layout, careful selection
of colours and well placed clear navigation buttons. It also has a common alarm
indication at the top of the page.
Good Screen

The ‘Bad’
screen is less than satisfactory. The layout is poor, the plant representation
isn't logical and the screen layout makes it difficult to locate the data. Poor
selection of colours, excessive use of capitals in a serif font and repetitive
use of units with all data values, makes this a really difficult screen to read
- especially at a glance or from a distance. The display lacks any clear
navigation routes to access other pages. More seriously, the display lacks any
form of alarm indication.
Bad Screen

We hope that in preparing this paper, many of the common failures can be avoided.
Whatever style you adopt when designing an HMI display, it most important that the style should be followed
throughout the suite of displays. Each display should have the same look and
feel; navigation buttons should be in the same place and everything should line
up.
Display pages need to be clear, easy to use and legible across a control desk:
-
Backgrounds - use muted tones – light grey is good.
-
Shadowing
is a recommended method for subdividing a display.
-
Background graphics should use muted tones, alarm colours should be avoided.
-
Use black
outlines to highlight objects.
-
Text –
use a standard font, which will be available on all PC’s.
-
Use
San serif fonts for on-screen clarity – e.g. Arial.
-
Text size
needs to be large enough to read at a distance e.g. Arial 16.
-
More
detailed text should be added as pop-up windows or ‘tool-tips’.
-
System
Alarm status should be visible on all displays.
-
Alarm
status should be displayed across the top of the display.
-
Alarm
colours will follow the convention: Red = alarm, Yellow = warning, green =
status OK.
-
For
Alarms - use additional non-colour dependent indications; position, text,
etc.
-
Flashing
of unaccepted alarms and automatic screen switching on alarm should be
avoided.
-
Sounds
are a good method for highlighting and prioritising alarms.
-
Dynamic
data should be positioned on scanned areas of the screen; i.e. across the
top, centrally and lower right.
-
Data
should be grouped logically.
-
Data
values should be clear & units should be obvious (but not repeated with
every value).
-
Data
Resolution should be appropriate to use, avoid too many decimal values;
546.45 C is pointless and unclear.
-
If red &
green are used for ‘Running’ & ‘Stopped’ indications, add text to make
it clear.
-
Plant
status indication must not rely solely upon colour changes.
-
Colour
combinations should be chosen with care and use appropriate colours and
contrasts.
-
Navigation buttons should be obvious and large enough to select quickly.
-
‘Next
Screen’ button should be ideally placed at the lower right side of the
screen.
-
A ‘Home /
Overview’ button should appear on each screen (ideally lower left corner).
-
Other
navigation buttons are best placed at the bottom of screen.
-
Control
buttons must invoke a ‘confirm action’ dialog box.
-
All pages
must have a consistent look & feel. Navigation buttons should be in the
same place.
-
Everything should line up.